Multi-mode optical fiber is a type of optical fiber mostly used for communication over short distances, such as within a building or on a campus. Multi-mode links can be used for data rates up to 800 Gbit/s. Multi-mode fiber has a fairly large core diameter that enables multiple light modes to be propagated and limits the maximum length of a transmission link because of modal dispersion. The standard G.651.1 defines the most widely used forms of multi-mode optical fiber.

Applications

The equipment used for communications over multi-mode optical fiber is less expensive than that for single-mode optical fiber.[1] Typical transmission speed and distance limits are 100 Mbit/s for distances up to 2 km (100BASE-FX), 1 Gbit/s up to 1000 m, and 10 Gbit/s up to 550 m.[2]

Because of its high capacity and reliability, multi-mode optical fiber generally is used for backbone applications in buildings. An increasing number of users are taking the benefits of fiber closer to the user by running fiber to the desktop or to the zone. Standards-compliant architectures such as Centralized Cabling and fiber to the telecom enclosure offer users the ability to leverage the distance capabilities of fiber by centralizing electronics in telecommunications rooms, rather than having active electronics on each floor.

Multi-mode fiber is used for transporting light signals to and from miniature fiber optic spectroscopy equipment (spectrometers, sources, and sampling accessories) and was instrumental in the development of the first portable spectrometer.

Multi-mode fiber is also used when high optical powers are to be carried through an optical fiber, such as in laser welding.

Comparison with single-mode fiber

The main difference between multi-mode and single-mode optical fiber is that the former has much larger core diameter, typically 50–100 micrometers—much larger than the wavelength of the light carried in it. Because of the large core and also the possibility of large numerical aperture, multi-mode fiber has higher "light-gathering" capacity than single-mode fiber. In practical terms, the larger core size simplifies connections and also allows the use of lower-cost electronics such as light-emitting diodes (LEDs) and vertical-cavity surface-emitting lasers (VCSELs) which operate at the 850 nm and 1300 nm wavelength (single-mode fibers used in telecommunications typically operate at 1310 or 1550 nm[3]). However, compared to single-mode fibers, the multi-mode fiber bandwidth–distance product limit is lower. Because multi-mode fiber has a larger core size than single-mode fiber, it supports more than one propagation mode; hence it is limited by modal dispersion, while single mode is not.

The LED light sources sometimes used with multi-mode fiber produce a range of wavelengths and these each propagate at different speeds. This chromatic dispersion is another limit to the useful length for multi-mode fiber optic cable. In contrast, the lasers used to drive single-mode fibers produce coherent light of a single wavelength. Because of the modal dispersion, multi-mode fiber has higher pulse spreading rates than single mode fiber, limiting multi-mode fiber's information transmission capacity.

Single-mode fibers are often used in high-precision scientific research because restricting the light to only one propagation mode allows it to be focused to an intense, diffraction-limited spot.

Jacket color is sometimes used to distinguish multi-mode cables from single-mode ones. The standard TIA-598C recommends, for non-military applications, the use of a yellow jacket for single-mode fiber, and orange or aqua for multi-mode fiber, depending on type.[4] Some vendors use violet to distinguish higher performance OM4 communications fiber from other types.[5]

Types

Multi-mode fibers are described by their core and cladding diameters. Thus, 62.5/125 μm multi-mode fiber has a core size of 62.5 micrometres (μm) and a cladding diameter of 125 μm. The transition between the core and cladding can be sharp, which is called a step-index profile, or a gradual transition, which is called a graded-index profile. The two types have different dispersion characteristics and thus different effective propagation distances.[6] Multi-mode fibers may be constructed with either graded or step-index profile.[7]

In addition, multi-mode fibers are described using a system of classification determined by the ISO 11801 standard — OM1, OM2, and OM3 — which is based on the modal bandwidth of the multi-mode fiber. OM4 (defined in TIA-492-AAAD) was finalized in August 2009,[8] and was published by the end of 2009 by the TIA.[9] OM4 cable supports 125 m links at 40 and 100 Gbit/s. The letters OM stand for 'optical multi-mode'.

For many years 62.5/125 μm (OM1) and conventional 50/125 μm multi-mode fiber (OM2) were widely deployed in premises applications. These fibers easily support applications ranging from Ethernet (10 Mbit/s) to gigabit Ethernet (1 Gbit/s) and, because of their relatively large core size, were ideal for use with LED transmitters. Newer deployments often use laser-optimized 50/125 μm multi-mode fiber (OM3). Fibers that meet this designation provide sufficient bandwidth to support 10 Gigabit Ethernet up to 300 meters. Optical fiber manufacturers have greatly refined their manufacturing process since that standard was issued and cables can be made that support 10 GbE up to 400 meters. Laser optimized multi-mode fiber (LOMMF) is designed for use with 850 nm VCSELs.

Older FDDI grade, OM1, and OM2 fiber can be used for 10 Gigabit Ethernet through 10GBASE-LRM. This requires the SFP+ interface to support electronic dispersion compensation (EDC) however, so not all switches, routers and other equipment can use these SFP+ modules.

The migration to LOMMF/OM3 has occurred as users upgrade to higher speed networks. LEDs have a maximum modulation rate of 622 Mbit/s because they cannot be turned on/off fast enough to support higher bandwidth applications. VCSELs are capable of modulation over 10 Gbit/s and are used in many high speed networks.

Some 200 and 400 Gigabit Ethernet speeds (e.g. 400GBASE-SR4.2) use wavelength-division multiplexing (WDM) even for multi-mode fiber[10] which is outside the specification for OM4 and lower. In 2017, OM5 has been standardized by TIA and ISO for WDM MMF, specifying not only a minimum modal bandwidth for 850 nm but a curve spanning from 850 to 953 nm.

Cables can sometimes be distinguished by jacket color: for 62.5/125 μm (OM1) and 50/125 μm (OM2), orange jackets are recommended, while aqua is recommended for 50/125 μm "laser optimized" OM3 and OM4 fiber.[4] Some fiber vendors use violet for "OM4+". OM5 is officially colored lime green.

VCSEL power profiles, along with variations in fiber uniformity, can cause modal dispersion which is measured by differential modal delay (DMD). Modal dispersion is caused by the different speeds of the individual modes in a light pulse. The net effect causes the light pulse to spread over distance, introducing intersymbol interference. The greater the length, the greater the modal dispersion. To combat modal dispersion, LOMMF is manufactured in a way that eliminates variations in the fiber which could affect the speed that a light pulse can travel. The refractive index profile is enhanced for VCSEL transmission and to prevent pulse spreading. As a result, the fibers maintain signal integrity over longer distances, thereby maximizing the bandwidth.

Comparison

Minimum reach of Ethernet variants over multi-mode fiber
Jacket color and categoryMinimum modal bandwidth
850 / 953 / 1300 nm
Fast Ethernet 100BASE-FX1 Gb (1000 Mb) Ethernet 1000BASE-SX1 Gb (1000 Mb) Ethernet 1000BASE-LX10 Gb Ethernet 10GBASE-SR10 Gb Ethernet 10GBASE-LRM (requires EDC)25 Gb Ethernet 25GBASE-SR40 Gb Ethernet40GBASE-SWDM440 Gb Ethernet 40GBASE-SR4100 Gb Ethernet 100GBASE-SR10
  FDDI (62.5/125)160 / – / 500 MHz·km2000 m[11] 220 m[12] 550 m[13] (mode-conditioning patch cord required)[14] [15] 26 m[16] 220 m[17] Not supportedNot supportedNot supportedNot supported
OM1 (62.5/125)200 / – / 500 MHz·km275 m33 m220 mNot supportedNot supportedNot supportedNot supported
OM2 (50/125)500 / – / 500 MHz·km550 m82 m220 mNot supportedNot supportedNot supportedNot supported
OM3 (50/125) *Laser Optimized*1500 / – / 500 MHz·km550 m (No mode-conditioning patch cord should be used.)300 m220 m70 m240m[18] Duplex LC100 m (330 m QSFP+ eSR4)100 m
OM4 (50/125) *Laser Optimized*3500 / – / 500 MHz·km400 m[19] >220 m100 m350mDuplex LC150 m (550 m QSFP+ eSR4[20]) 150 m
OM5 (50/125) "Wideband multi-mode" for short-wave WDM[21] 3500 / 1850 / 500  MHz·km>220 m100 m

Encircled flux

The IEC 61280-4-1 (now TIA-526-14-B) standard defines encircled flux which specifies test light injection sizes (for various fiber diameters) to make sure the fiber core is not over-filled or under-filled to allow more reproducible (and less variable) link-loss measurements.[22]

See also

References

External links

Notes and References

  1. Web site: Multimode Fiber for Enterprise Networks . Telecommunications Industry Association . Jun 4, 2008 . https://web.archive.org/web/20090604210103/http://www.fols.org/technology/ . June 4, 2009 . dead .
  2. Web site: OM4 - The next generation of multimode fiber . Furukawa Electric North America . May 16, 2012 . https://web.archive.org/web/20140422141312/http://www.fols.org/fols_library/white_papers/documents/OFSOM4TheNextGenerationofMultimodeFiber.pdf . April 22, 2014 . dead .
  3. Web site: Fiber Optic Cable Tutorial . ARC Electronics . Oct 1, 2007 . March 4, 2015 . https://web.archive.org/web/20181023040952/https://arcelect.com/fibercable.htm . October 23, 2018 . dead .
  4. Web site: Fiber optic cable color codes . Tech Topics . . Sep 17, 2009.
  5. Web site: Who is Erika Violet and what is she doing in my data center? . Tech Topics . Belden . Dwayne . Crawford . Sep 11, 2013 . Feb 12, 2014.
  6. Web site: Optical Fibers Explained . British FibreOptic Industry Association . Apr 9, 2011.
  7. Web site: Fiber Optics Overview . 2012-11-23.
  8. Web site: Meeting Report #14 . Telecommunications Industry Association.
  9. Web site: Next generation fiber arrives . Paul . Kish . 2010-01-01 .
    1. Cabling Networking Systems
    . Business Information Group.
  10. IEEE 802.3 Clause 150
  11. Web site: 100BASE-FX Technical Brief . Hewlett-Packard Development Company, L.P. . 2007 . Nov 20, 2012 . dead . https://web.archive.org/web/20121009212203/http://www.hp.com/rnd/pdfs/100FXtechbrief.pdf . 2012-10-09 .
  12. IEEE 802.3-2012 Clause 38.3
  13. IEEE 802.3 38.4 PMD to MDI optical specifications for 1000BASE-LX
  14. Web site: Cisco Mode-Conditioning Patch Cord Installation Note . Cisco Systems, Inc . 2009 . Feb 20, 2015.
  15. As with all multi-mode fiber connections, the MMF segment of the patch cord should match the type of fiber in the cable plant (Clause 38.11.4).
  16. Web site: Cisco 10GBASE X2 Modules Data Sheet . Cisco . June 23, 2015.
  17. Web site: What is a 10GBASE-LRM transceiver and why do I need it? . CBO GmbH . December 3, 2019.
  18. Web site: 40GE SWDM4 QSFP+ Optical Transceiver Finisar Corporation. www.finisar.com. en. 2018-02-06.
  19. Web site: IEEE 802.3 . 31 October 2014.
  20. Web site: 40G Extended Reach with Corning Cable Systems OM3/OM4 Connectivity with the Avago 40G QSFP+ eSR4 Transceiver . 14 August 2013 . 2013 . Corning.
  21. Web site: TIA Updates Data Center Cabling Standard to Keep Pace with Rapid Technology Advancements . TIA . 2017-08-09 . 2018-08-27.
  22. Web site: Goldstein. Seymour. Encircled flux improves test equipment loss measurements. Cabling Installation & Maintenance. 1 June 2017.