Integral windup explained

Integral windup, also known as integrator windup[1] or reset windup,[2] refers to the situation in a PID controller where a large change in setpoint occurs (say a positive change) and the integral term accumulates a significant error during the rise (windup), thus overshooting and continuing to increase as this accumulated error is unwound (offset by errors in the other direction).

Solutions

This problem can be addressed by

Occurrence

Integral windup particularly occurs as a limitation of physical systems, compared with ideal systems, due to the ideal output being physically impossible (process saturation: the output of the process being limited at the top or bottom of its scale, making the error constant). For example, the position of a valve cannot be any more open than fully open and also cannot be closed any more than fully closed. In this case, anti-windup can actually involve the integrator being turned off for periods of time until the response falls back into an acceptable range.

This usually occurs when the controller's output can no longer affect the controlled variable, or if the controller is part of a selection scheme and it is selected right.

Integral windup was more of a problem in analog controllers. Within modern distributed control systems and programmable logic controllers, it is much easier to prevent integral windup by either limiting the controller output, limiting the integral to produce feasible output, or by using external reset feedback, which is a means of feeding back the selected output to the integral circuit of all controllers in the selection scheme so that a closed loop is maintained.

Notes and References

  1. Web site: Microchip Application Note AN532: Servo Control of a DC Motor. 4. Microchip Technology, Inc.. 1997. 2014-01-07.
  2. Web site: Discretised PID Controllers. M. Tham. 2014-01-07. 2020-03-28. https://web.archive.org/web/20200328032533/https://d721700c-a-62cb3a1a-s-sites.googlegroups.com/site/occasionalnotes/control-system-math/minimum-jerk/digitalpid/Discrete%20PID%20Controllers.pdf?attachauth=ANoY7cpaAtndh1d_19Za1oLNPhge2rs8QVfmjiqBcwi4X9Jyc2NgIeyiUPxAzgh6KdXG1DtHluhPOvD6DScBdss-p2tHW5fY2g9t9SMfRx68RBLiS_1AumWf5YV9wZmX8T2DB2K85J3slm2VtiaGPnp7O7kpddjYkjPA3ymmb1kbZTGngfOC5-3MV8rZjRRBsbNBCEUYasfEx7TV11qQZc1m3xTZUCVWkZxKfFBNCzwHpsxIsyqxBILm-RHYzva46ZRzsmZzKMvy7eTCWKFWTsq938VCiiNNOoky11eIQwlXADXLnGlQTzY%3D&attredirects=1. dead.
  3. Book: 1989 . 1693–1698 . 10.23919/ACC.1989.4790464 . 36848080 . http://cse.lab.imtlucca.it/~bemporad/teaching/controllodigitale/pdf/Astrom-ACC89.pdf . Integrator Windup and How to Avoid It . 1989 American Control Conference . Astrom . Karl Johan . Rundqwist . Lars .
  4. Web site: Beauregard . Brett . Improving the Beginner's PID: Reset Windup . Project Blog . 2021-11-21.
  5. Web site: Cooper. Douglas. Integral (Reset) Windup, Jacketing Logic and the Velocity PI Form. 2014-02-18.
  6. Book: Aström . Karl . Control System Design . 2002 . 228–231 .
  7. Book: Zheng . Jinchuan . Guo . Yuqian . Fu . Minyue . Wang . Youyi . Xie . Lihua . 2007 IEEE International Conference on Control Applications . Improved Reset Control Design for a PZT Positioning Stage . 2007 . https://ieeexplore.ieee.org/document/4389410 . 1272–1277 . 10.1109/CCA.2007.4389410. 1959.13/937597 . 978-1-4244-0442-1 . 14877444 .
  8. Hollot . C.V. . 1997 . Revisiting Clegg Integrators: Periodicity, Stability and IQCs . IFAC Proceedings Volumes . 30 . 27 . 31–38 . 10.1016/S1474-6670(17)41154-2. subscription .