In thermodynamics, the heat transfer coefficient or film coefficient, or film effectiveness, is the proportionality constant between the heat flux and the thermodynamic driving force for the flow of heat (i.e., the temperature difference,). It is used in calculating the heat transfer, typically by convection or phase transition between a fluid and a solid. The heat transfer coefficient has SI units in watts per square meter per kelvin (W/m2K).
The overall heat transfer rate for combined modes is usually expressed in terms of an overall conductance or heat transfer coefficient, . In that case, the heat transfer rate is:
Q |
=hA(T2-T1)
Q |
h
A
T2
T1
The general definition of the heat transfer coefficient is:
h=
q | |
\DeltaT |
q
q=d
Q |
/dA
\DeltaT
The heat transfer coefficient is the reciprocal of thermal insulance. This is used for building materials (R-value) and for clothing insulation.
There are numerous methods for calculating the heat transfer coefficient in different heat transfer modes, different fluids, flow regimes, and under different thermohydraulic conditions. Often it can be estimated by dividing the thermal conductivity of the convection fluid by a length scale. The heat transfer coefficient is often calculated from the Nusselt number (a dimensionless number). There are also online calculators available specifically for Heat-transfer fluid applications. Experimental assessment of the heat transfer coefficient poses some challenges especially when small fluxes are to be measured (e.g.).[1] [2]
A simple method for determining an overall heat transfer coefficient that is useful to find the heat transfer between simple elements such as walls in buildings or across heat exchangers is shown below. This method only accounts for conduction within materials, it does not take into account heat transfer through methods such as radiation. The method is as follows:
1 | |
U ⋅ A |
=
1 | |
h1 ⋅ A1 |
+
dxw | |
k ⋅ A |
+
1 | |
h2 ⋅ A2 |
Where:
U
A
A1
A2
k
h
dxw
As the areas for each surface approach being equal the equation can be written as the transfer coefficient per unit area as shown below:
1 | |
U |
=
1 | |
h1 |
+
dxw | |
k |
+
1 | |
h2 |
or
U=
1 | ||||||||||
|
Often the value for
dxw
In the walls of buildings the above formula can be used to derive the formula commonly used to calculate the heat through building components. Architects and engineers call the resulting values either the U-Value or the R-Value of a construction assembly like a wall. Each type of value (R or U) are related as the inverse of each other such that R-Value = 1/U-Value and both are more fully understood through the concept of an overall heat transfer coefficient described in lower section of this document.
Tf
Ts
{{T}infty
{{T}f
Recommendations by Churchill and Chu provide the following correlation for natural convection adjacent to a vertical plane, both for laminar and turbulent flow.[3] [4] k is the thermal conductivity of the fluid, L is the characteristic length with respect to the direction of gravity, RaL is the Rayleigh number with respect to this length and Pr is the Prandtl number (the Rayleigh number can be written as the product of the Grashof number and the Prandtl number).
h =
k | |
L |
\left({0.825+
| |||||||||
\left(1+(0.492/Pr)9/16\right)8/27 |
For laminar flows, the following correlation is slightly more accurate. It is observed that a transition from a laminar to a turbulent boundary occurs when RaL exceeds around 109.
h =
k | |
L |
\left(0.68+
| |||||||||
\left(1+(0.492/Pr)9/16\right)4/9 |
\right) 10-1<RaL<109
For cylinders with their axes vertical, the expressions for plane surfaces can be used provided the curvature effect is not too significant. This represents the limit where boundary layer thickness is small relative to cylinder diameter
D
D | |
L |
\ge
35 | |||||||||
|
where
GrL
And in fluids of Pr ≤ 6 when
D | |
L |
\ge
25.1 | |||||||||
|
Under these circumstances, the error is limited to up to 5.5%.
W. H. McAdams suggested the following correlations for horizontal plates.[6] The induced buoyancy will be different depending upon whether the hot surface is facing up or down.
For a hot surface facing up, or a cold surface facing down, for laminar flow:
h =
| |||||||||
L |
105<RaL<2 x 107
and for turbulent flow:
h =
| |||||||||
L |
2 x 107<RaL<3 x 1010.
For a hot surface facing down, or a cold surface facing up, for laminar flow:
h =
| |||||||||
L |
3 x 105<RaL<3 x 1010.
The characteristic length is the ratio of the plate surface area to perimeter. If the surface is inclined at an angle θ with the vertical then the equations for a vertical plate by Churchill and Chu may be used for θ up to 60°; if the boundary layer flow is laminar, the gravitational constant g is replaced with g cos θ when calculating the Ra term.
For cylinders of sufficient length and negligible end effects, Churchill and Chu has the following correlation for
10-5
12 | |
<Ra | |
D<10 |
h =
k | |
D |
\left({0.6+
| |||||||||
\left(1+(0.559/Pr)9/16\right)8/27 |
For spheres, T. Yuge has the following correlation for Pr≃1 and
1\leRaD\le105
{Nu
For heat flow between two opposing vertical plates of rectangular enclosures, Catton recommends the following two correlations for smaller aspect ratios.[8] The correlations are valid for any value of Prandtl number.
For
1<
H | |
L |
<2
h =
k | |
L |
0.18\left(
Pr | |
0.2+Pr |
RaL\right)0.29 RaLPr/(0.2+Pr)>103
where H is the internal height of the enclosure and L is the horizontal distance between the two sides of different temperatures.
For
2<
H | |
L |
<10
h =
k | |
L |
0.22\left(
Pr | |
0.2+Pr |
RaL\right)0.28\left(
H | |
L |
\right)-1/4 RaL<1010.
For vertical enclosures with larger aspect ratios, the following two correlations can be used. For 10 < H/L < 40:
h =
k | |
L |
0.42
1/4 | |
Ra | |
L |
Pr0.012\left(
H | |
L |
\right)-0.3 1<Pr<2 x 104, 104<RaL<107.
For
1<
H | |
L |
<40
h =
k | |
L |
0.46
1/3 | |
Ra | |
L |
1<Pr<20, 106<RaL<109.
For all four correlations, fluid properties are evaluated at the average temperature—as opposed to film temperature—
(T1+T2)/2
T1
T2
T1>T2
See main article Nusselt number and Churchill–Bernstein equation for forced convection over a horizontal cylinder.
Sieder and Tate give the following correlation to account for entrance effects in laminar flow in tubes where
D
{\mu}b
{\mu}w
NuD={1.86} ⋅ {{{\left(Re ⋅ Pr\right)}{1\diagup{}3 }}}{{\left(
D | |
L |
\right)}{1\diagup{}3 }}{{\left(
{{\mu | |
b |
For fully developed laminar flow, the Nusselt number is constant and equal to 3.66. Mills combines the entrance effects and fully developed flow into one equation
NuD=3.66+
| |||||
|
The Dittus-Bölter correlation (1930) is a common and particularly simple correlation useful for many applications. This correlation is applicable when forced convection is the only mode of heat transfer; i.e., there is no boiling, condensation, significant radiation, etc. The accuracy of this correlation is anticipated to be ±15%.
For a fluid flowing in a straight circular pipe with a Reynolds number between 10,000 and 120,000 (in the turbulent pipe flow range), when the fluid's Prandtl number is between 0.7 and 120, for a location far from the pipe entrance (more than 10 pipe diameters; more than 50 diameters according to many authors[10]) or other flow disturbances, and when the pipe surface is hydraulically smooth, the heat transfer coefficient between the bulk of the fluid and the pipe surface can be expressed explicitly as:
{hd\overk}={0.023}\left({jd\over\mu}\right)0.8\left({\mucp\overk}\right)n
where:
d
k
\mu
j
cp
n
The fluid properties necessary for the application of this equation are evaluated at the bulk temperature thus avoiding iteration.
In analyzing the heat transfer associated with the flow past the exterior surface of a solid, the situation is complicated by phenomena such as boundary layer separation. Various authors have correlated charts and graphs for different geometries and flow conditions.For flow parallel to a plane surface, where
x
L
There exist simple fluid-specific correlations for heat transfer coefficient in boiling. The Thom correlation is for the flow of boiling water (subcooled or saturated at pressures up to about 20 MPa) under conditions where the nucleate boiling contribution predominates over forced convection. This correlation is useful for rough estimation of expected temperature difference given the heat flux:[12]
\DeltaT\rm=22.5 ⋅ {q}0.5\exp(-P/8.7)
where:
\DeltaT\rm
q is the heat flux, MW/m2
P is the pressure of water, MPa
This empirical correlation is specific to the units given.
The resistance to the flow of heat by the material of pipe wall can be expressed as a "heat transfer coefficient of the pipe wall". However, one needs to select if the heat flux is based on the pipe inner or the outer diameter.Selecting to base the heat flux on the pipe inner diameter, and assuming that the pipe wall thickness is small in comparison with the pipe inner diameter, then the heat transfer coefficient for the pipe wall can be calculated as if the wall were not curved:
h\rm={2k\overx}
k
x
If the above assumption does not hold, then the wall heat transfer coefficient can be calculated using the following expression:
h\rm={2k\over{d\rmln(d\rm/d\rm)}}
where
di
do
The thermal conductivity of the tube material usually depends on temperature; the mean thermal conductivity is often used.
For two or more heat transfer processes acting in parallel, convective heat transfer coefficients simply add:
h=h1+h2+ …
For two or more heat transfer processes connected in series, convective heat transfer coefficients add inversely:[13]
{1\overh}={1\overh1}+{1\overh2}+...
For example, consider a pipe with a fluid flowing inside. The approximate rate of heat transfer between the bulk of the fluid inside the pipe and the pipe external surface is:[14]
q=\left({1\over{{1\overh}+{t\overk}}}\right) ⋅ A ⋅ \DeltaT
q
h
t
k
A
\DeltaT
The overall heat transfer coefficient
U
For the case of a heat exchanger,
U
q=UA\DeltaTLM
where:
q
U
A
\DeltaTLM
The overall heat transfer coefficient takes into account the individual heat transfer coefficients of each stream and the resistance of the pipe material. It can be calculated as the reciprocal of the sum of a series of thermal resistances (but more complex relationships exist, for example when heat transfer takes place by different routes in parallel):
1 | |
UA |
=\sum
1 | |
hA |
+\sumR
where:
R = Resistance(s) to heat flow in pipe wall (K/W)
Other parameters are as above.[15]
The heat transfer coefficient is the heat transferred per unit area per kelvin. Thus area is included in the equation as it represents the area over which the transfer of heat takes place. The areas for each flow will be different as they represent the contact area for each fluid side.
The thermal resistance due to the pipe wall (for thin walls) is calculated by the following relationship:
R=
x | |
kA |
where
x
k
This represents the heat transfer by conduction in the pipe.
The thermal conductivity is a characteristic of the particular material. Values of thermal conductivities for various materials are listed in the list of thermal conductivities.
As mentioned earlier in the article the convection heat transfer coefficient for each stream depends on the type of fluid, flow properties and temperature properties.
Some typical heat transfer coefficients include:
Often during their use, heat exchangers collect a layer of fouling on the surface which, in addition to potentially contaminating a stream, reduces the effectiveness of heat exchangers. In a fouled heat exchanger the buildup on the walls creates an additional layer of materials that heat must flow through. Due to this new layer, there is additional resistance within the heat exchanger and thus the overall heat transfer coefficient of the exchanger is reduced. The following relationship is used to solve for the heat transfer resistance with the additional fouling resistance:[16]
1 | |
UfP |
1 | + | |
UP |
RfH | + | |
PH |
RfC | |
PC |
where
Uf
style\rm
W | |
m2K |
P
\rmm
U
style\rm
W | |
m2K |
RfC
style\rm
m2K | |
W |
RfH
style\rm
m2K | |
W |
PC
\rmm
PH
\rmm
This equation uses the overall heat transfer coefficient of an unfouled heat exchanger and the fouling resistance to calculate the overall heat transfer coefficient of a fouled heat exchanger. The equation takes into account that the perimeter of the heat exchanger is different on the hot and cold sides. The perimeter used for the
P
UP
The fouling resistances can be calculated for a specific heat exchanger if the average thickness and thermal conductivity of the fouling are known. The product of the average thickness and thermal conductivity will result in the fouling resistance on a specific side of the heat exchanger.
Rf
df | |
kf |
where:
df
\rmm
kf
style\rm
W | |
mK |